Ethernet(Modbus TCP) I/O Module

Modbus TCP I/O Module(16 bit 4-ch Analogue Output-AO)

Ethernet Remote I/O Module with 16 bit 4-ch Analog Output

Modbus TCP Analog IO Module(16 bit 4 AO)

Product Introduction (NET-6000M Series)

NET-6000M Ethernet-based data acquisition and control modules provide I/O, data acquisitions, and networking in one module to build a cost effective, distributed monitoring and control solution for a wide variety of applications. With Ethernet-based technology, NET-6000M series modules build up a cost-effective DA&C system for building automation, environmental monitoring, and manufacturing applications. Modbus has become a standard communication, and is now the most commonly available means of connecting industrial. This makes the NET-6000M series perfect for integration with HMI, SCADA, PLC and other software systems

Features and benefits:

  • 32 bits & 120M high speed CPU, the real time embedded OS.
  • Power or dual power(Analogue Modules): Independent isolation
  • Surge protection: 15KV
  • The analogue input: Magnetic coupling isolation and protection.
  • The input voltage can be positive and negative, each channel has TVS and ESD protection.
  • The measuring range can be shifted by software.
  • The single end and differential can be shifted by software. Single end can be changed to 16 channels by software.
  • The ID and baud rate can be adjusted by rotary button directly.
  • Enclosure: shielded metal 
  • The differential sampling frequency can reach 50Hz/channel

Hardware Specification:

System

CPU

32-bit 120MIPS CPU

Operation System

Real-Time

Watchdog

Yes

Communication

RS-6000M

CAN-6000T

NET-6000M

 

RS485

CAN

Ethernet

10/100 Base-TX

LED Display

Power Indicator

Red

Run Indicator

Green

Error Indicator

Red

Link Indicator

Green

Act Indicator

Yellow

Mechanical

Dimensions

(W x H x D)(mm)

140*110*40

Installation

DIN-Rail mounting

Environment

Operating Temperature

-20℃~+70℃

Storage Temperature

-30℃~+80℃

Power Requirements

Power Input

+9V~30V DC

Power Consumption

<3W

I/O Specification:

Model

NET-6031M

NET-6032M

Analog Output

Output Channels

4

Output Range

±10V, ±5V, 0V~5V, 0V~10V

0~20mA(Built-in 250ohm Resistor)

4~20mA(Built-in 250ohm Resistor)

Resolution

12-bit

16-bit

Accuracy

±0.1%

±0.01%

Max Current Load Resistance

Internal power +15 V: 500 Ω.

External power +24 V: 1000 Ω.

Isolation

2500V

Protection

Built-in TVS/ESD Protection

±4 kV Contact for each terminal

Ordering Information:

1.2 Odering Information (NET-6000M Series Modbus TCP Protocol)

Model

Description

Digital I/O

NET-6011M

Ethernet Remote I/O Module with16-ch DI

NET-6012M

Ethernet Remote I/O Module with16-ch DO

NET-6013M

Ethernet Remote I/O Module with 8-ch DI and 8-ch DO

Relay Output

NET-6014M

Ethernet Remote I/O Module with 5-ch Relay(Form A)

NET-6015M

Ethernet Remote I/O Module with 5-ch Relay(3-ch Form A, 2-ch Form C)

Analog Input

NET-6021M

Ethernet Remote I/O Module with 12bit 16-ch Single End AI or 8-ch differential AI

NET-6022M

Ethernet Remote I/O Module with 16bit 16-ch Single End AI or 8-ch differential AI

Analog Output

NET-6031M

Ethernet Remote I/O Module with 12bit 4-ch AO

NET-6032M

Ethernet Remote I/O Module with 16bit 4-ch AO

RTD

NET-6041M

Ethernet Remote I/O Module with 5-ch RTD

Thermocouple

NET-6042M

Ethernet Remote I/O Module with 5-ch TC

Mixed

NET-6088

Ethernet Remote I/O Module with 16bit 8-ch Single End AI or 4-ch differential AI, 12bit 4-ch AO, 2-ch DI, 2-ch DO

REQUEST A QUOTE

* You can also contact us for a quote by E-mail: sales@buenoptic.net

Please type your full name.
Invalid Input
Invalid email address.
Invalid Input
Invalid Input