CAN Bus Remote I/O Module with 5xTC
CAN Data Acquisition Module 5 channels of thermocouple
Product Introduction (CAN-6000T Series)
CAN-6000T CAN-based data acquisition and control modules provide I/O, data acquisitions, and networking in one module to build a cost effective, distributed monitoring and control solution for a wide variety of applications. With CAN-based technology, CAN-6000T series modules build up a cost-effective DA&C system for building automation, environmental monitoring, and manufacturing applications.
Features and benefits:
- 32 bits & 120M high speed CPU, the real time embedded OS.
- Power or dual power(Analogue Modules): Independent isolation
- Surge protection: 15KV
- The analogue input: Magnetic coupling isolation and protection.
- The input voltage can be positive and negative, each channel has TVS and ESD protection.
- The measuring range can be shifted by software.
- The single end and differential can be shifted by software. Single end can be changed to 16 channels by software.
- The ID and baud rate can be adjusted by rotary button directly.
- Enclosure: shielded metal
- The differential sampling frequency can reach 50Hz/channel
- The CAN IO module can work with our CAN repeater, CAN switch, CAN PCI, CAN to Ethernet and CAN fiber optic extender to combine a complete CAN bus network system.
Hardware Specification:
System |
|||
CPU |
32-bit 120MIPS CPU |
||
Operation System |
Real-Time |
||
Watchdog |
Yes |
||
Communication |
RS-6000M |
CAN-6000T |
NET-6000M |
|
RS485 |
CAN |
Ethernet 10/100 Base-TX |
LED Display |
|||
Power Indicator |
Red |
||
Run Indicator |
Green |
||
Error Indicator |
Red |
||
Link Indicator |
Green |
||
Act Indicator |
Yellow |
||
Mechanical |
|||
Dimensions (W x H x D)(mm) |
140*110*40 |
||
Installation |
DIN-Rail mounting |
||
Environment |
|||
Operating Temperature |
-20℃~+70℃ |
||
Storage Temperature |
-30℃~+80℃ |
||
Power Requirements |
|||
Power Input |
+9V~30V DC |
||
Power Consumption |
<3W |
I/O Specification:
Model |
CAN-6042T |
|
Thermocouple Input |
||
Input Channels: |
5 |
|
Input Type |
J |
-210℃~1200℃ |
|
K |
-200℃~1370℃ |
|
E |
-100℃~1000℃ |
|
T |
-200℃~400℃ |
|
N |
-200℃~1300℃ |
|
B |
650℃~1800℃ |
|
R |
0℃~1750℃ |
|
S |
0℃~1760℃ |
Input Impedance: |
1.5M |
|
ADC Resolution |
24-bit |
|
Temperature Resolution |
0.1℃ |
|
Accuracy: |
±0.1% or Better |
|
Sampling Rate: |
All channels: 5 samples/sec Per channel: 1samples/sec |
|
Isolation |
2500V |
|
Protection |
Built-in TVS/ESD Protection ±4 kV Contact for each terminal |
Ordering Information:
Odering Information (CAN-6000T CAN Bus Series)
Model |
Description |
Digital I/O |
|
CAN-6011T |
CAN Remote I/O Module with16-ch DI |
CAN-6012T |
CAN Remote I/O Module with16-ch DO |
CAN-6013T |
CAN Remote I/O Module with 8-ch DI and 8-ch DO |
Relay Output |
|
CAN-6014T |
CAN Remote I/O Module with 5-ch Relay(Form A) |
CAN-6015T |
CAN Remote I/O Module with 5-ch Relay(3-ch Form A, 2-ch Form C) |
Analog Input |
|
CAN-6021T |
CAN Remote I/O Module with 12bit 16-ch Single End AI or 8-ch differential AI |
CAN-6022T |
CAN Remote I/O Module with 16bit 16-ch Single End AI or 8-ch differential AI |
Analog Output |
|
CAN-6031T |
CAN Remote I/O Module with 12bit 4-ch AO |
CAN-6032T |
CAN Remote I/O Module with 16bit 4-ch AO |
RTD |
|
CAN-6041M |
CAN Remote I/O Module with 5-ch RTD |
Thermocouple |
|
CAN-6042M |
CAN Remote I/O Module with 5-ch TC |
Mixed |
|
CAN-6088 |
CAN Remote I/O Module with 16bit 8-ch Single End AI or 4-ch differential AI, 12bit 4-ch AO, 2-ch DI, 2-ch DO |