BE's CAN to Fiber Optic Converters are isntalled in the fire alarm system in Bulgraria ,which successfully solved the distance limit problem and greatly improved the safety of the system.

DeviceNet Fiber Optic Converter(No Cascading)

Model: FO-FIB-100PT

Description:

The DeviceNet series products provide an optical point-to-point or multi-drop bus network connection for DeviceNet data interfaces on one or two, multi mode or single mode optical fibers. The DeviceNet Point-to-Point fiber optic converter units operate as the end or terminal points and provide an electrical connection and a two fiber optical connection. The units support CAN 1.0 and CAN 2.0 CAN standards, and Device Net. And are transparent to all high level protocols.It adopts the latest technology in the world,it can be transmitted to 20Km when it's at the baud rate of 125/250/500K.

Product Features

  • Up to 500K data rate(Support high rate and long distance transmission)
  • Baud rate Configurable,by software and rotary button
  • Multimode and singlemode
  • Single fiber solution
  • Buffering: 1000 frames/second
  • Wall mount, rack or chassis configurations
Specification:
Data
Data Formats CAN1.0 ,CAN2.0 , Device Net
CAN Data Rate 125/250/500K
Bit Error Rate <1 x 10-12
Connectors
Data Screw Block Terminal
Fiber ST, SC or FC (ST fitted as standard)
Environmental
Operating   Temperat ure - 3 0 C--- +70 C
Storage Temperature - 40 C--- +85 C
Operating   Humidity 0- 95%
MTBF >100,000 Hours
Optical
Fiber Multi mode or single mode
Wavelength MM: 850/1550nm, SM: 1310/1550nm
Number of fibers 2 or 1
POWER
Power Input +9 to +40V DC
Mechanical
Dimensions 156(W)×108(D)×33.6(H )mm Wall Mount & DIN Rail

IEC101/102/103/104 to Modbus RTU or TCP Gateway

 

BUE-801 series IEC-60870 to Modbus Gateways can provides both industrial communication device and solution of the whole industrial automation system,which plays more important roles in industrial control and automation,especially in the substation automation.

1.Communication function:

Protocol conversion:

Standard protocols that BUE-801 support: UCA2,TCP/IP, Serial, DNP3,OPC, Modbus RTU/TCP, IEC60870-5 series(IEC101,IEC102,IEC103,IEC104),or IEC61850. All the protocols can communicate with any one protocol in our protocol list.

Non-standard protocol: DC screen,power meter,safety equipments.The different protocols of data can convert with each other in the BUE-801


Data processing:

Digital processing: signal acquisition & transmission,anti-shake,singnal maintenance, timing alarm, quality judgment.
Analog processing: multiplication coefficient, residual cleared, anti-mutation, quality judgment,etc.

Point table custom and information split:

In the  system it provides different data forwarding point tables,different channels’ protocol  can forward and each uses different data forwarding table. The same data can be submitted to the upper machine in the form of different value.


Dual channel processing:

BUE-801 Supports the system with dual channel mode and the upper machine communication, including fully redundant dual channel way, communication link redundancy, main equipment and so on.


Measuring point self description:

BUE-801 supports self description of data point, which is convenient for maintenance and debugging.


2.Advanced application:

Data calculation:

BUE-801 provides standard calculation formula and take the processing of data in the way of  addition, subtraction, multiplication, division, logic judgment (including greater than, less than, equal to, is not equal to, greater than or equal to, less than or equal to, logic and logic, logic or, not), sine, cosine, square root, take maximum, minimum, average calculation.

Equipment automatic control can be set up:


BUE-801 provides the setting of basic control logic, timing or logical calculation according to the real-time data of on-site equipment start-stop switch quantity control and analog control, such as temperature, pressure, etc.

Advanced equipment control integration

3.Management function:

Debugging management:

BUE-801 provides all kinds of debugging methods and management, including remote debugging, intelligent device simulation, data simulation, control block, data browsing, message and debugging information monitoring, message storage and playback, flow rate and bit error rate statistics.

Equipment management:

Equipment management functions includes: remote diagnosis and maintenance, hardware watchdog, custom information indicator, main standby switch management etc.

Time synchronization:

BUE-801 can receive the time code from time servers,it can synchronizes time in the format of IRIG-B and NTP/SNTP.

4.System feature:

Low lantency: 5 to 50ms lantency.

Strong data processing ability.

Reliable communication management


5. Technical specifications:
Hardware:
10/100MTCP/IP:  2-6 nos
RS422/232/485    4-16 nos
DI/DO   8 nos
LED lights:  8nos
Wireless(GPRS/Zigbee/wifi/BD)  1 nos

Software:
Maximum channels:200
Maximum digital number/channel: 65536
Maximum analog number/channel: 65536
Maximum electric degree/channel:   65536
Maximum output/channel: 65536
Maximum analog output/channel: 65536
Data forwarding base: 4
Minimum data processing lantency: 5ms
Time synchronization precision:<1ms(Hardware synchronization)

Technical specs

400Mhz Freescale MPC8308 CPU

128M DDR2 Memory

128M Nand Flash

2 Ethernet Ports

4 RS-232/485 Isolation Serial Ports

DIN-Rail Mount

System

CPU

Freescale MPC8308 PowerPC CPU,400MHz

Memory

DDR2 128M

Flash

8M Nor Flash

128M Nand Flash

Operating System

Linux 2.6.29.6

LED

 

System:Power x1,RUN x1,

LAN:10/100/1000M x4(Link x2 Act x2)

Serial:TxD x4,RxD x4

Others

RTC,Buzzer,Watchdog Timer,Reset button,Console Port x1

Serial Communication

Console Port

Console Port RJ45 connector x1

RS232 115200bps N,8,1

Serial Port

4 xRS-232/485 TB Interface connector

software-selectable

RS-232 Signals:TxD,RxD,GND

RS-485 Signals:485A(Data+),485B(Data-)

Protection

Built-in 15KV ESD protection for all signals, 2KV iCoupler digital isolation protection

Network Communication

LAN

Auto-sensing 10/100/1000Mbps x 2, RJ45

Build-in 1.5KV magnetic isolation protection

Power Requirements

Power Input

Dual Power Input Design

PWR1:9-48VDC or 9-48VAC

PWR2:9-48VDC or 9-48VAC

Lost power alarm

Relay empty node

Power Consumption

 

 

8W@12VDC

Mechanical

Dimensions

200(L)x121.01(W)x54.1(H)

Installation

DIN-Rail Mount

Environmental

Operating Temperature

-20-60℃

Storage Temperature

-30-80℃

Regulatory Approvals and Warranty

EMC

GB/T 17626.2-2006 Class 4

GB/T 17626.4-2008 Class 4

GB/T 17626.5-2008 Class 4

GB/T 17626.6-2008 Class 3

Warranty

5 Years

Heavy-duty Industrial Grade Modbus RTU to TCP Gateway

Ethernet :10/100 Mbps, RJ45, Auto MDI/MDIX

Protection: Built-in 1.5 KV magnetic isolation

Modbus data format: Modbus RTU/ASCII ,Modbus TCP/IP

Connector: RS-485 or RS-232

No. Of Ports: 1 port  RS-232 (DB9) or RS-485(Terminal)   The Modbus RS-485 or RS-232 port number can be extended.

Serial Line Protection: 15 KV ESD for all signals

Surge Protection: 600W

Isolation: 2KV

Serial Communication Parameters

Parity None, Even, Odd, Space, Mark

Data Bits 7, 8

Stop Bits 1, 2

Flow Control RTS/CTS, XON/XOFF

Transmission Speed 50 bps to 250Kbps

Software Features
Operation Mode: RTU Slave, RTU Master, ASCII Slave, ASCII Master
Utilities: MGate Manager
Multi-Masters and: 16 simultaneous TCP masters, 32 simultaneous requests for each TCP

Housing: Metal case(11.5x8.3x2.7CM) 

Multi-Request: Master
Power Requirements
Power Input 9 to 24VDC

Operating Temperature: -40 to 80C

Storage Temperature: -45 to 85C

Safety: EN 60950-1
EMC,CE, FCC
EMI: EN 55022 Class A, FCC Part 15 Subpart B Class A
EMS: EN 55024
Power Line Protection:
EN 61000-4-4(EFT) Level 2,
EN 61000-4-5(Surge) Level 3

GB/T 17626.2-2006 Class 4

GB/T 17626.4-2008 Class 4

GB/T 17626.5-2008 Class 4

GB/T 17626.6-2008 Class 3

Warranty: 5 Years

 

 

Substation Communication Gateway(Industrial PC)

 

8016 series 1U rack substation embedded computer for substation communication can provides both industrial communication device and solution of the whole power and industrial automation system,which plays more important roles in industrial control and automation,especially in the substation automation.

 

1.Protocols it can support:

 

UCA2,TCP/IP, DNP3, OPC, Modbus RTU,RS-232,RS-485/422,Modbus TCP, IEC60870-5 series(IEC101,IEC102,IEC103,IEC104), IEC61850,NTP/SNTP,IRIG-B and other substation communication protocols.

 

Feature:

400Mhz Freescale MPC8308 CPU

128M DDR2 Memory

128M Nand Flash

6 Ethernet Ports

16 RS-232/485 Isolation Serial Ports

AC85~265V Input

Specifications:

System

CPU

Freescale MPC8308 PowerPC CPU,400MHz

Memory

DDR2 128M

Flash

8M NorFlash

128M NandFlash

Operating System

Linux 2.6.29.6

 

LED

 

8016

System:Power x1,RUN x1,PWR1 Alarm x1,PWR2 Alarm x1

LAN:Link x6 & Act x6 Indicators

Serial Port:Transfer x16 & receive x16 Indicators

Function LED:2 x4 Indicators

Others

RTC,Buzzer,Watchdog Timer,Reset button,Console Port x1

Serial Communication

Console Port

Console Port DB9 connector x1

RS232 115200Bps N,8,1

Serial Port

16 x RS-232/485 TB Interface connector

Software Mode select

RS-232 Signals:TXD,RXD,GND

RS-485 Signals:485A(Data+),485B(Data-)

Baud:300~115200Bps

Protection

Built-in 15KV ESD protection for all signals, 2KV iCoupler digital isolation protection

Network Communication

LAN

 

8016

Auto-sensing 10/100/1000Mbps x 2, RJ45

Auto-sensing 10/100Mbps x 4, RJ45

Build-in 2KV iCoupler digital isolation protection

Optional

Digital Input Port

4 x Isolation Input

VL:≦80V

VH:>85V

Digital Output Port

4 x Relay Output

VL:≦80V

VH:>85V

CAN Port

CAN2.0B(Isolation protection)

Baud:5Kbps~1Mbps

IRIG-B Port

RS-485(Isolation protection)

Precision:±1us

Power Requirements

Power Input

Dual Power Input Design

PWR1:  85~265VDC or  100~265VAC

PWR2:  85~265VDC or  100~265VAC

Lost power alarm

Relay empty node(Limited to single power)

Power alarm indicators

Power Consumption

 

 

10W@220VAC

Mechanical

Dimensions

483(L)x226.7(W)x44(H)(Maximum size)

Installation

Rack Mount 1U

Environmental

Operating Temperature

-20-60℃

Storage Temperature

-30-80℃

Regulatory Approvals and Warranty

EMC

GB/T 17626.2-2006 Class 4

GB/T 17626.4-2008 Class 4

GB/T 17626.5-2008 Class 4

GB/T 17626.6-2008 Class 3

Warranty

5 Years